UNIPOS Series

Hybrid UPS (UES) with both UPS and PCS functions

  • True On-Line Double Conversion UPS / High-reliability, high-quality power supply
  • Transformerless structure / high efficiency, compact size, light weight
  • Input high power factor control / PF=0.99
  • Input power factor harmonic minimization / 5% or less
  • 100% digital control method / stable AC power supply with high reliability
  • Inverter output voltage each phase control / robust against unbalanced load
  • Grid reactive power compensation function / lagging 0.8 ~ leading 0.8 power factor control
  • Convenient user interface (Korean language support) / Graphic LCD module (Option)
  • Various communication interfaces (protocols) / RS-232, RS-485 (Modbus RTU)

시스템 구성도

UPS SPECIFICATION

 

Capacity(KVA)1015203040506075801001251501602002503004005006008001000
Electrical features
AC
InputPhase3-phase 4-wire system + GND
Rated voltage
(Available range)
 380 / 220 V (± 15 % / rated, at -50 % / 50 % load)
Rated frequency
(Available range)
50, 60 Hz (± 5 %)
Waveform distortion
(THD-A)
5% or less
Power factor0.98 or more
OutputPhase3-phase 4-wire system
Rated voltage
(Voltage stability)
 380 / 220 V (± 2 %)
Rated frequency
(Available range)
50, 60 Hz (within ±0.5 %, when the inverter is Free Running)
Waveform distortion
(THD-V)
3% linear (5% non-linear)
Overload capacity120% 10 minutes, 150% 10 seconds
Power factor0.8
Performance
Efficiency (%)-10 KVA or less 88% or more / -Over 10 KVA 30 KVA or less 92% or more
-Over 30 KVA 75 KVA or less 92.5% or more / -Over 75 KVA 150 KVA or less 93% or more
-Over 150 KVA 300 KVA or less 94% or more / -Over 300 KVA 94% or more
Switchover time 4 ms or less
Capacity(KVA)3568101520253040506810152025304050
Electrical features
AC
InputPhase1-phase 2-wire + GND3-phase 3-wire or 3-phase 4-wire + GND
Rated voltage
(Available range)
220V (±10%)380V (±10%)
Rated frequency
(Available range)
50, 60Hz (±5%)50, 60Hz (±5%)
Waveform distortion
(THD-A)
5% or less5% or less
Power factor0.98 or more0.98 or more
OutputPhase1-phase 2-wire
Rated voltage
(Voltage stability)
220V (±2%)
Rated frequency
(Available range)
50, 60 Hz (within ±0.5 %, when the inverter is Free Running)
Waveform distortion
(THD-V)
3% linear (5% non-linear)
Overload capacity120% 10 minutes, 150% 10 seconds
Power factor0.8
Performance
Efficiency (%)-Over 1 KVA 5 KVA or less 85% or more / -Over 5 KVA 20 KVA or less 88% or more
-Over 20 KVA 30 KVA or less 92% or more / -Over 30 KVA 50 KVA or less 92.5% or more
Switchover time4 ms or less
User environment data
Operating temperature
(Humidity)
0 ℃ ~ 40 ℃ (95 %)
Storage temperature
(Humidity)
 -20 ℃ ~ 60 ℃ (95 %)
Noise100 KVA or less : 65 dB(A) or less / Over 100 KVA : 75 dB(A) or less
AltitudeBelow 1,000 m above sea level, indoor (for indoor use)
Outer case standard / paintingIP20 / EA404K (Hamma Tone, White)

 

※ The product specifications above are subject to change without notice to improve function and quality.