UPS Parallel Technology
KUKJE ELECTRIC. MFG. CO., LTD.

New technology for UPS parallel operation

Comparison between the existing parallel control method (communication method) and the new parallel operation technology method using magnetic load sharing transformer

Existing parallel control method (communication method)

  • Need to share each load current (I1, I2) information
    - Requires high speed communication
    - Vulnerable to external noise
    - In case of sudden load change, load sharing error occurs
    (※time delay on communication speed and digital controller)
  • Need extra current controller for load sharing
  • Limited quantities of parallel operations
  • Transformer type UPS

New parallel operation technology method using magnetic load sharing transformer

  • No need to share information on each load current (I1, I2)
  • Magnetic load sharing transformer
    - No high-speed communication required
    - Resistant to external noise
    - Load sharing error is very small in the event of a sudden change in load
  • No current controller required for load sharing
  • No limit on the number of parallel operations. (Suitable for multiple parallel operations)
  • Increased reliability by not sharing load by communication method
  • Easy parallel scalability in the future
  • Transformer-free type UPS
기존 병렬제어 방식 (통신방식)자기 부하분담 변압기에 의한 병렬운전 신기술
▶ 각 부하전류(I1, I2) 정보 공유 필요
- 고속 통신 필요
- 외부 잡음에 취약함
- 부하 급변시, 부하 분담 오차 존재
(※통신 속도 및 디지털 제어기 시간 지연 존재)
▶ 부하분담용 전류 제어기 추가 필요
▶ 병렬 운전 수량 제한
▶ 변압기형 UPS
▶ 각 부하전류(I1, I2) 정보 공유 불필요
▶ 자기 부하분담 변압기
- 고속 통신 불필요
- 외부 잡음에 강함
- 부하 급변시, 부하 분담 오차 매우 적음
(※자기적인 부하분담 기능 : V1 × I1 = V2 × I2)
▶ 부하분담용 전류 제어기 불필요
▶ 병렬 운전 수량 제한 없음.(다수 병렬운전에 적합)
▶ 통신방식으로 부하분담을 하지 않으므로 신뢰성 증대
▶ 향후 병렬 확장성 용이함
▶ 무변압기형 UPS

UPS Parallel System